FLHA for electrical panel replacement
Provincial OHS law requires hazards to be assessed and controlled before work starts. A field level hazard assessment (FLHA) for electrical panel replacement is done on site at the start of the shift and again whenever conditions change.
It lists the tasks, hazards and controls, and every worker signs on before starting and signs off at the end of the shift. The main hazards are disturbing asbestos, electric shock from live wiring, lifting and carrying heavy loads and falling from a ladder.
FLHA example: electrical panel replacement
This is a complete FLHA for electrical panel replacement, with 10 job steps. Open it in the builder to add your site, crew and signatures, change anything, and download a PDF. Or download the free Word template below and fill it in by hand.
Job steps, hazards and controls
| # | Job step | Hazards | Risk before | Controls | Risk after |
|---|---|---|---|---|---|
| 1 | Tell the occupants when the power will be off and arrange a supply for medical or other critical equipment |
| Medium |
| Low |
| 2 | Set up barriers and good lighting at the electrical panel so no one else can reach the open board |
| Medium |
| Low |
| 3 | Check the old electrical panel backing board and surrounds for asbestos |
| Critical |
| Medium |
| 4 | Arrange the supply disconnection, isolate, apply lockout and tags, then test to prove dead; treat the supply side as live until it is disconnected |
| Critical |
| Medium |
| 5 | Check the tester on a known live source before and after proving dead |
| Critical |
| Medium |
| 6 | Remove the old electrical panel, labelling every circuit as it comes off |
| Critical |
| Medium |
| 7 | Mount the new enclosure, drilling with dust control and working from a stable step |
| High |
| Medium |
| 8 | Terminate circuits with GFCI protection and tighten connections to the right torque |
| High |
| Medium |
| 9 | With your lock still on, do the dead tests: ground continuity, insulation resistance, polarity and correct circuit connections |
| Critical |
| Medium |
| 10 | Remove your lock only when the dead tests pass and everyone is clear, re-energise, then test GFCI trip times and polarity live; label the electrical panel, clean up and issue the certificate |
| Critical |
| Medium |
PPE
Plant and equipment
Permits and plans
Emergency
Call 911. Add the nearest hospital, the muster point and the first aid attendant for your site.
Sign-off
Supervisor and every worker sign to confirm they have read and understood this FLHA, then sign off at the end of the shift.
Free FLHA template for electrical panel replacement
Word (.docx) and PDF, Letter landscape, no email needed. Fill in your site details, then print or send it.
Make yours in 2 minutes
Same document, filled in for your job. Answer a few yes or no questions, the crew signs on the phone, and you send the PDF.
Pre-start checklist for electrical panel replacement
Tick these off before work starts. They come from the hazards, permits and equipment in this job.
- FLHA read, explained and signed by everyone on the job
- Ladder inspected, secured and extending 1 m above the landing
- Lockout, tagout and test before touch done before work starts
- Asbestos register or survey checked for the work area
- First aid attendant, first aid kit and emergency number (911) confirmed
- PPE checked and worn: CSA green triangle safety boots (CSA Z195), safety glasses (CSA Z94.3), rubber insulating gloves, arc flash PPE (CSA Z462)
The safe sequence of work
- Tell the occupants when the power will be off and arrange a supply for medical or other critical equipment
- Set up barriers and good lighting at the electrical panel so no one else can reach the open board
- Check the old electrical panel backing board and surrounds for asbestos
- Arrange the supply disconnection, isolate, apply lockout and tags, then test to prove dead; treat the supply side as live until it is disconnected
- Check the tester on a known live source before and after proving dead
- Remove the old electrical panel, labelling every circuit as it comes off
- Mount the new enclosure, drilling with dust control and working from a stable step
- Terminate circuits with GFCI protection and tighten connections to the right torque
- With your lock still on, do the dead tests: ground continuity, insulation resistance, polarity and correct circuit connections
- Remove your lock only when the dead tests pass and everyone is clear, re-energise, then test GFCI trip times and polarity live; label the electrical panel, clean up and issue the certificate
Hazards to watch on electrical panel replacement
The hazards most specific to this job, and the step where each one comes up.
What changes on your site
This example covers the job itself. Your site may add more. Add controls for any of these that apply (the builder asks you these as yes or no questions):
- Could anyone fall 3 metres or more, or fall any distance into machinery, water, a hazardous substance or through an opening?
- Will anyone work on a roof?
- Is there a fragile roof, skylight or clear roof sheet?
- Will you use a scaffold or mobile tower?
- Will you use an aerial work platform (scissor lift or boom lift)?
Why FLHAs get rejected
Prime contractors and COR auditors send documents back for these reasons. This example avoids them, but check yours too.
- End of shift boxes already say "None" when the form was signed at the start of the shift.
- One FLHA reused for days or weeks, or a "review by" date a month away, when the work and conditions change daily.
- No time of assessment and no record of any revision, which Alberta s.7(3) requires.
- Workers signed that they "read" it, but nothing shows they took part, which Alberta s.8(1) requires.
- Work at height with no fall protection plan where the province requires one, or no written rescue procedure for workers using fall arrest.
- Permits or locates required on site but no permit or ticket numbers recorded.
- No re-assessment entry after an obvious change such as weather, a new task or a new crew member.
Rules by province for electrical panel replacement
| Province or territory | Key local rule | Regulator |
|---|---|---|
| Ontario | Fall protection (O. Reg. 213/91 s.26) applies at a fall of more than 3 m, more than 1.2 m where the work area is used as a path for a wheelbarrow or similar equipment, and at any height into operating machinery, water or other liquid, a hazardous substance, or through an opening. | Ontario Ministry of Labour, Immigration, Training and Skills Development |
| British Columbia | Fall protection is required where a fall of 3 m or more may occur (s.11.2). A written fall protection plan is required at 7.5 m or more where there are no permanent guardrails (s.11.3). | WorkSafeBC |
| Alberta | A hazard assessment must be done before work begins, and before a new work site is built (OHS Code s.7(1)). The results must be written down with the controls (s.7(2)). | Alberta Occupational Health and Safety |
| Quebec | Guardrails (Safety Code s.2.9.1, as amended by Decret 63-2025) are needed where a worker could fall into liquid or a hazardous substance, onto moving parts or dangerous equipment, 1.2 m or more when using a vehicle, 1.5 m or more when handling a load, and more than 3 m in all other cases. | CNESST (Commission des normes, de l'equite, de la sante et de la securite du travail) |
| Manitoba | A prime contractor is required whenever more than one employer or self employed person works on the site at the same time (Act s.7). | Manitoba Workplace Safety and Health Branch |
| Saskatchewan | An occupational health committee is required at 10 or more workers of one employer (Act s.3-22). | Saskatchewan Ministry of Labour Relations and Workplace Safety, OHS Division |
| Nova Scotia | Workers must be trained in fall protection before using it or working in, supervising or planning work in a fall protection area, with a refresher at least every 3 years (WHSR s.21.19). | Nova Scotia Department of Labour, Skills and Immigration, Safety Branch (OHS) |
| New Brunswick | Fall protection is needed from 3 m above water or the nearest permanent safe level (Reg 91-191 s.49(1)(a)(i)). | WorkSafeNB |
| Newfoundland and Labrador | Give written notice to the minister before starting a construction project that will last 30 days or more, with the site, location, type of work and number of workers (Regs s.8). | Government Services, Occupational Health and Safety Division |
| Prince Edward Island | Fall protection is needed from 3 m above the nearest safe surface or water (Fall Protection Regulations s.2(1)(a)). | Workers Compensation Board of PEI, OHS Division |
| Yukon | Every employer must do hazard assessments with the committee, representative or workers, and redo them after significant changes or incidents (Regs s.1.03.01). | Yukon Workers' Safety and Compensation Board |
| Northwest Territories | Fall protection is needed from 3 m, or lower if there is a risk of injury (s.119(1)). Guardrails are needed for falls of 1.2 m to 3 m at permanent work sites (s.119(2)). | Workers' Safety and Compensation Commission (WSCC) |
| Nunavut | No 911. To reach the RCMP in an emergency, dial your community's first three digits then 1111 (Iqaluit: 979-1111). Put the local fire, ambulance and RCMP numbers on every FLHA. | Workers' Safety and Compensation Commission (WSCC) |
Questions
Do I need an FLHA for electrical panel replacement?
Provincial OHS law requires hazards to be assessed and controlled before work starts. A field level hazard assessment (FLHA) for electrical panel replacement is done on site at the start of the shift and again whenever conditions change.
Who signs the FLHA?
The supervisor and every worker take part in the assessment and sign on before work starts, then sign off at the end of the shift. Review it and re-sign whenever the task or conditions change.
How long do I keep it?
Keep completed hazard assessments for at least 3 years (COR auditors sample the last 12 months). Review this FLHA and re-sign whenever the task, crew or conditions change.
What PPE is needed for electrical panel replacement?
Usually CSA green triangle safety boots (CSA Z195), Safety glasses (CSA Z94.3), Rubber insulating gloves, Arc flash PPE (CSA Z462), N95 respirator, High-visibility vest (CSA Z96), Respirator fit tested to CSA Z94.4 (P100 for dust, or the type the air test calls for), Coveralls, Work gloves, Cut-resistant gloves, Hearing protection, Hard hat (CSA Z94.1), Knee pads. The site rules may add more, so check with the general contractor.
More electrical FLHAs
Related jobs in other trades
Toolbox talks for this job
Blank FLHA template: free FLHA templates. Also for other countries: Australia (SWMS) · United Kingdom (RAMS) · United States (JHA)